Hygienic stratification buffer tank HSK-SLS

Hygienic stratification buffer tank HSK-SLS

The HSK exclusive version ...

Heating buffer tank with integrated big stainless steel corrugated tube for legionella safe preparation of DHW, with large dimensioned oval tube heat exchangers. The area of application ranges from single-family houses to hotels and industrial buildings. Available standard sizes 500, 800, 1000, 1250, 1500 und 2200 litres, each type with one stainless steel heat exchanger and two solar heat exchangers. The HSK exclusive version - highest efficiency of solar input and tap water output. With patented thermo-hydraulic stratification system SLS® - unique in its category!


Hygienic preparation of DHW and heating efficiently due to SLS® system


The hygienic stratification buffer tank HSK-SLS, with integrated Spiro-HT-stainless steel DHW heat exchanger, is perfectly suitable for the preparation of hygienic tap hot water. You will achieve excellent performance values due to the Spiro-HT-technology, which qualifies the tank for either high performance or heat pump installations.

It also qualifies for the integration of versatile heat sources with its patented thermo-hydraulic stratification system SLS®. The heat management can be realized with very low control effort due to its exact stratification characteristics. The integration of thermal solar energy via the two very large dimensioned oval solar heat exchanger provides for a heat transmission that optimizes the efficiency factor of the solar panels.

Established systems are combined in a smart way. The hygienic stratification buffer tank HSK-SLS is therefore the perfect heat center for new buildings, as well as for renovations of old buildings. The high DHW output qualifies the tank for the application in single family as well as in multifamily houses. An intelligent hydraulic connection of several hygienic stratification buffer tanks HSK-SLS even enable the application in large scale plants as well as housing blocks, hotels and diverse industrial objects. In the hygienic stratification buffer tank HSK-SLS our established Solarbayer‐specific HSK system is combined with the patented stratification system SLS®.



Take advantage of these benefits
  • versatile connection possibilities
  • perfect heat stratification due to the patented stratification system SLS®
  • insulation thickness 100 mm, available either as fleece ISO-B1 or flexible foam insulation
  • high quality steel S235JR
  • large dimensioned solar oval tube exchanger, top and bottom
  • legionella-safe hygienic DHW preparation
  • stainless steel corrugated hose 1.4404 with DVGW authorization
  • high tap hot water output
  • installation of an electric heating element possible



Successful detail solutions





Technical specifications

Hygienic straticification buffer tank HSK-SLS   500 800 1000 1250 1500 2200
nominal capacity L 492 788 926 1123 1422 2204
height with insulation [A] mm 1720 1910 2090 2080 2220 2170
height without insulation [B] mm 1645 1835 2015 2005 2145 2095
tilted height mm 1700 1950 2100 2130 2250 2300
diameter with insulation [C] mm 850 990 990 1100 1200 1450
diameter without insulation [D] mm 650 790 790 900 1000 1250
insulation thickness mm 100 100 100 100 100 100
weight approx. kg 158 214 240 290 302 413
max. operating temperature buffer tank °C 95 95 95 95 95 95
max. operating pressure buffer tank bar 6 6 6 6 6 6
max. size of electric heating element (optional) kW 4,5 6 6 6 9 9

stand-by heat loss according to EN 12897:2006,
with fleece insulation ISO-B1
  500 800 1000 1250 1500 2200
standby heat loss W 103 123 132 149 166 205
energy efficiency class   C -- -- -- -- --
efficiency label   PDF -- -- -- -- --

stand-by heat loss according to EN 12897:2006,
with flexible foam insulation
  500 800 1000 1250 1500 2200
standby heat loss W 118 141 152 172 201 243
energy efficiency class   D -- -- -- -- --
efficiency label   PDF -- -- -- -- --

specifications stainless steel DHW heat exchanger   500 800 1000 1250 1500 2200
capacity DHW L 75 96 96 111 111 126
heating surface 7,2 9,0 9,0 10,5 10,5 12
continuous tap output at 17 kW, TSP 65°C | CW 10°C/HW 45°C L/h 480 510 510 522 522 540
continuous tap output at 27 kW, TSP 65°C | CW 10°C/HW 45°C L/h 685 735 735 750 750 790
continuous tap output at 50 kW, TSP 65°C | CW 10°C/HW 45°C L/h 1090 1345 1345 1380 1380 1465
Ø stainless steel DHW heat exchanger mm 48 48 48 48 48 48
max. operating pressure DHW heat exchanger bar 8 8 8 8 8 8
max. operating temperature DHW heat exchanger °C 95 95 95 95 95 95
pressure drop (2 m³/h) mbar 67 104 104 128 128 158

specifications solar heat exchanger top   500 800 1000 1250 1500 2200
heating surface solar heat exchanger top 1,3 2 3 3 3,5 4,2
capacity solar heat exchanger top L 6,2 8 12 12 14 16,8
pressure drop heat exchanger top (2 m³/h) mbar 69 88 111 111 156 179
heating surface solar heat exchanger bottom 2,3 3 3 3 3 5,5
capacity solar heat exchanger bottom L 10,4 12 12 12 12 22
pressure drop heat exchanger bottom (2 m³/h) mbar 70 112 112 112 112 214
max. operating pressure bar 10 10 10 10 10 10
max. operating temperature °C 110 110 110 110 110 110
recommended min. collector surface 10 14 17 20 23 31

connections with dimensioning   500 800 1000 1250 1500 2200
[1] de-airing (Rp 1 ½″)   top top top top top top
[2] sensor (Rp ½″)   oben oben oben oben oben oben
[3] flow line boiler/heating (Rp 1 ½″, Rp 2″ *) mm 1510 1690 1870 1835 1935 1850
[4] flow line boiler/heating (Rp 1 ½″, Rp 2″ *) mm 1510 1690 1870 1835 1935 1850
[5] sensor/thermometer (Rp ½″) mm 1420 1590 1770 1735 1835 1845
[6] hot water outlet (Rp 1 ¼″) mm 1410 1580 1760 1725 1825 1835
[7] flow solar top (Rp 1″) mm 1320 1440 1650 1585 1735 1735
[8] sensor solar top (Rp ½″) mm 1220 1290 1370 1405 1435 1445
[9] return solar top (Rp 1″) mm 1120 1160 1270 1165 1235 1295
[10] electric heating element (Rp 1 ½″) mm 1000 1060 1140 1045 1125 1175
[11] flow boiler/heating (Rp 1 ½″) mm 900 930 1100 885 1075 1130
[12] flow boiler/heating (Rp 1 ½″) mm 900 930 1100 885 1075 1130
[13] flow solar bottom (Rp 1″) mm 800 830 990 765 935 1045
[14] return boiler/heating (Rp 1 ½″) mm 670 730 890 665 835 925
[15] return boiler/heating (Rp 1 ½″) mm 670 730 890 665 835 925
[16] sensor/thermometer (Rp ½″) mm 670 730 770 665 835 845
[17] solar sensor bottom (Rp ½″) mm 440 470 470 495 535 545
[18] return solar bottom (Rp 1″) mm 340 370 370 395 435 445
[19] cold water inlet (Rp 1 ¼″) mm 240 270 270 295 335 335
[20] return boiler/heating (Rp 1 ½″, Rp 2″ *) mm 150 170 170 195 235 320
[21] return boiler/heating (Rp 1 ½″, Rp 2″ *) mm 150 170 170 195 235 320

* from HSK-SLS 2200 on the connections are Rp 2″



Manufacturing tolerance according to DIN ISO 13920 C
Please take the instructions for installation/start up/maintenance from the relevant operation manuals




Further product informations


Brochure heat storage tanks
Brochure
heat storage tanks

16-page brochure, DIN A4
PDF-file, 1.2 MB

pdf DOWNLOAD

Manual hygienic stratification buffer tank HSK-SLS
Manual
hygienic stratification buffer tank HSK-SLS

16-page brochure, DIN A5
PDF-Datei, 0.58 MB

pdf DOWNLOAD